Hong Kong's Buildings Energy Efficiency Ordinance: What the 2025 Changes Mean for Your Lighting
Buildings use about 90% of Hong Kong's electricity, and lighting is one of the four installations the Buildings Energy Efficiency Ordinance controls. The law was tightened in 2025, and the main changes took effect on 20 September 2026. If you own, manage or fit out a building in Hong Kong, here is what changed and what it means for your lights.

What the law is
The Buildings Energy Efficiency Ordinance (Cap. 610), or BEEO, has been fully in force since 21 September 2012. EMSD runs it. It covers air-conditioning, electrical, lift and escalator, and lighting installations.
It does two main things:
New buildings and major retrofitting works in existing buildings must meet the Building Energy Code (BEC).
Certain buildings must have regular energy audits, done to the Energy Audit Code.
The 2024 editions of both codes have been fully in force since 23 August 2025. EMSD says their standards are more than 20% higher than the 2015 edition.
What changed in 2025
The Buildings Energy Efficiency (Amendment) Ordinance 2025 was passed in June 2025 and gazetted on 20 June 2025. It came in two stages:
20 September 2025: more qualifications accepted for registration as a Registered Energy Assessor (REA).
20 September 2026: everything else.
From 20 September 2026:
Data centres are covered. Stand-alone data centres and data centre parts of industrial buildings were added, so 15 types of buildings must now meet the BEC, up from 13.
More buildings need energy audits. The list went from 2 types (commercial buildings and the commercial parts of composite buildings) to 11. It now includes buildings mainly used for education, community services, municipal services, and medical and health care, as well as government office buildings, airport passenger terminals, railway stations and data centres.
Small buildings are exempt from audits. Buildings with a gross floor area of 7,000 m² or less don't need one, unless they are data centres.
Audits every 5 years, not every 10.
Audit data goes public. For audits starting on or after 20 September 2026, EMSD publishes technical data from the report, including the efficiency, years in service, control system and energy-saving potential of the main installations.
Who it affects
Owners and managers of commercial buildings, hotels, public-service buildings and data centres, plus the common areas of residential, industrial and composite buildings. Tenants are affected too: for work inside a unit, the "responsible person" (owner, tenant or occupier) must get the paperwork. So are the contractors and engineers who specify and install the lighting.
What it means for lighting
Lighting power density (LPD)
LPD is the wattage of the fixed lighting in a space, at full output, divided by its floor area, in W/m². The BEC counts circuit wattage, so driver and control gear losses are included.
BEC 2024 sets a maximum LPD for each type of space, and many limits are lower than in BEC 2021. A large office (over 200 m²) went from 7.8 to 7.2 W/m², a corridor from 7.0 to 6.0, and a car park from 4.0 to 3.0. A space with 70 W or less of fixed lighting is exempt from the limit.

Many spaces, including offices, corridors, lobbies and toilets, also need automatic lighting control that can switch off or cut lighting power by at least 50%. Each automatic control area can now cover no more than 250 m², down from 2,000 m² in BEC 2021.
When does a retrofit count as "major retrofitting"
Lighting work is major retrofitting when it adds or replaces lighting covering 500 m² or more of floor area, in one unit or common area, under the same series of works within 12 months. BEC Table 10.1 applies the lighting rules when the new or replacement fittings total 3 kW or more.

When it counts:
LPD limits apply if the area had no lights before, or the new fittings add up to more than 50% of the old wattage.
Lighting control rules apply if the area had no lights before, or the circuits are completely rewired.
Within 2 months of finishing, the owner of the common area, or the responsible person for the unit, must get a Form of Compliance from an REA.
After that, the lighting must be kept to at least that standard. EMSD's own example of a breach is swapping energy-saving tubes back to incandescent bulbs.
Energy audits
An audit covers the central building services. For lighting, EMSD's examples are the lights in the main entrance, common lift lobbies and common staircases. EMSD says an audit generally finds about 1% to 10% in electricity savings. With the new disclosure rule, those findings will be public.
Penalties
According to EMSD, the maximum fine is HK$50,000 for not getting a Form of Compliance within 2 months, not keeping the installation to that standard, not doing a required energy audit, or not displaying a valid Energy Audit Form at the main entrance. Ignoring an improvement notice can cost HK$25,000, plus HK$1,000 a day while it continues.
A checklist for building owners and managers

Check if your building is one of the 15 types, and if it now needs audits.
Ask an REA when your next, or first, audit is due.
List your lighting by space: type, wattage, quantity and age.
Compare the LPD of your main spaces with BEC 2024 Table 5.4.
Before a fit-out, add up the floor area across all phases in 12 months.
Bring in an REA before work starts.
Get spec sheets with circuit wattage for every fitting.
Keep the Form of Compliance on file.
How LED retrofits help
LPD is about watts, not lumens. A fitting that gives the same light for fewer watts lowers your LPD directly. This is where LED helps most.
Fewer watts for the same light. Replacing old fluorescent, metal halide or sodium fittings with good LED fittings usually cuts the wattage. Check the figures on each spec sheet rather than a general percentage.
Ready for controls. Many LED fittings can be dimmed and work with occupancy or daylight sensors.
Clear numbers. A proper spec sheet gives the wattage including the driver, which is what the BEC counts.

About Matsushima Lighting
Matsushima Lighting (H.K) Ltd has supplied LED lighting in Hong Kong since 2006, and we make our own fittings in our Shenzhen factory. We supply commercial, industrial, outdoor and residential lighting, and work with developers, architects and engineering firms. KMB and HAECO are among our clients.
We don't do energy audits, and we are not an REA. We supply the fittings, with full spec sheets, so your REA or engineer can check LPD and sign off the work. Planning a retrofit? Send us the floor area, ceiling height and the fittings you have now, and we'll suggest options.
Call +852 2951 0038 or WhatsApp +852 9635 1145. Our office is at Rm 1805-06, 18/F, Hollywood Plaza, 610 Nathan Road, Mong Kok.
FAQ
Does the BEEO cover my flat?
No. For residential buildings, it covers the common areas only.
We're replacing lights one floor at a time. Does that count?
It can. Works in the same series within 12 months are added together. If they reach 500 m² in one unit or common area, check with an REA.
Does outdoor lighting count?
No. The BEC excludes façade and outdoor lighting, lights under canopies over pavements or roads, plug-in lights and lighting built into signs.
Our school is 5,000 m². Do we need an energy audit?
No. Buildings of 7,000 m² gross floor area or less are exempt, unless they are data centres. The BEC still applies to new buildings and major retrofitting.
This article is general information, not legal advice. For the full rules, see EMSD's BEEO website: www.emsd.gov.hk/beeo