top of page

Smart Lighting for Hong Kong Offices, Factories and Warehouses: A Simple Guide

11月17日
讀畢需時 6 分鐘

Most Hong Kong buildings have already moved to LED, or are moving there now. That cut lighting energy and maintenance. Smart lighting is the next step: it is less about the light itself, and more about how the light is controlled.

What is smart lighting?

An ordinary LED is efficient, but it is either on or off. Someone has to flick a switch, or a timer does it.

A smart system adds sensors that detect people and daylight, controls that decide when lights should switch or dim, and a network, wired or wireless, that lets the parts talk to each other. Most systems also have software, so a facility manager can set schedules, see energy use and get an alert when a fitting fails.

You do not have to do everything at once. You can start with a sensor on one fitting or circuit, then move to a room or zone, then to a networked system for a floor or a building.

The main protocols

A protocol is the language the parts use to talk to each other. If it is open and certified, you can mix brands and add to the system later. If it is closed, you may be locked to one supplier.

Protocol

Wired or wireless

Open standard?

Best suited to

Main watch-outs

DALI-2 / D4i

Wired (2-wire bus)

Yes (IEC 62386, DALI Alliance certified)

Offices, retail, hotels and high-spec industrial

Needs control wiring; 64 drivers per line

Bluetooth NLC

Wireless mesh

Yes (Bluetooth SIG)

Retrofits, offices and warehouses

Check products are NLC qualified

Zigbee

Wireless mesh

Yes (Connectivity Standards Alliance)

Small commercial projects and mixed devices

Product interoperability varies

Casambi

Wireless mesh (Bluetooth LE)

No (proprietary platform)

Retail, hospitality and small offices

Single-platform ecosystem

KNX

Wired (mainly)

Yes (ISO/IEC 14543-3)

Whole-building automation on premium projects

Needs a KNX-trained integrator

LoRaWAN / NB-IoT

Wireless, long range

Yes

Street lighting, estates and remote sites

Low data rate; not for fast local control

For a new office fit-out, DALI-2 is the usual wired choice. It gives fitting-level control and two-way data, and D4i lets the fitting report energy use and faults. Where new control cables are hard to run, Bluetooth NLC or another certified wireless system is often faster to install. Outdoor and estate lighting usually uses LoRaWAN or NB-IoT.

What it can achieve

Lights can dim or switch off when a space is empty, dim near windows when there is enough daylight, follow opening hours, and be set to the level the work actually needs. A system can also report energy use and flag a failed fitting before someone complains.

The figures below come from independent research. They show what controls save on top of the lighting energy, not the savings from switching to LED.

A Lawrence Berkeley National Laboratory review of 88 studies in commercial buildings found average savings of 24% from occupancy sensors, 28% from daylighting and 38% when control methods were combined. A DesignLights Consortium study of networked lighting controls in 194 North American buildings found average savings of 49%, and 63% where every light had its own sensor.

These numbers vary a lot, depending on how the system is set up and how the space is used. They are overseas studies. We did not find a comparable published Hong Kong field study. The physics is the same, but operating hours, daylight and occupancy patterns differ.

This is an illustration only, not a quote or a promise. A warehouse with 100 LED high bays at 150 W, lit 12 hours a day, six days a week, costs about HK$79,000 a year at CLP's 2026 average net tariff of 140.6 cents per kWh. If occupancy sensors save the Lawrence Berkeley average of 24%, the saving is roughly HK$19,000 a year. HK Electric's 2026 average net tariff is 163.3 cents per kWh, so the same saving is worth more on Hong Kong Island and Lamma.

Why it matters in Hong Kong

Since 23 August 2025, the Building Energy Code 2024 has required automatic lighting control in many space types, including offices, conference rooms, corridors, lift lobbies, toilets, storerooms, loading areas and car parks (at parking spaces). The control must be able to switch off or reduce general lighting by at least 50%, unless the fixed lighting in that space is 150 W or less. Occupancy sensors must reduce lighting within 15 minutes of everyone leaving, or 10 minutes in car parks.

This applies to new buildings and to lighting refits of 500 m² or more in a unit or common area. It covers commercial buildings, hotels and the common areas of residential and industrial buildings, among others. In industrial buildings it covers the common areas, not the factory or warehouse floors themselves.

Since 20 September 2026, mandatory energy audits have been extended from commercial buildings to 11 building types, and the audit interval has been shortened from 10 years to 5 years. An audit will look at lighting. A system that records energy use makes savings easier to show.

For 2026, CLP's average net tariff is 140.6 cents per kWh and HK Electric's is 163.3 cents per kWh. Every kWh saved is worth well over HK$1.

Both power companies run funds that can help pay for lighting upgrades, but the terms change, so always check the current guide. CLP's Eco Building Fund can pay 30% to 50% of a retrofit in communal areas, including lighting. HK Electric's Smart Power Building Fund can pay 10%, 30% or 50% of the net eligible cost of communal work, including lighting, depending on the energy saved. Check eligibility before you sign a contract. Some schemes require that no work has started, and no contract has been awarded, before approval.

Where to start

Start where lights burn long hours in spaces that are often empty. Warehouses and logistics centres are a good first step: high bays with occupancy and daylight sensors, set to dim to a low background level rather than switch fully off. Car parks are often lit around the clock, and sensor dimming at parking spaces is required under the Building Energy Code. Corridors, lift lobbies, toilets, storerooms and loading bays are used in short bursts, and most already need automatic control under the code.

For a new office fit-out, DALI-2 is a safe wired choice. For a retrofit where cable is hard to run, a certified wireless system is often more practical. Ask for certified products, not just "compatible". Budget for proper set-up: poor commissioning is the most common reason savings fall short. Record a baseline, and read the fund rules before you award any contract.

A short glossary

Term

Plain explanation

DALI-2

Current certification for Digital Addressable Lighting Interface, the main open wired lighting standard.

D4i

A DALI-2 extension for drivers inside a fitting, adding energy and diagnostic data.

Bluetooth NLC

Bluetooth Networked Lighting Control: standard wireless profiles so different makers' products can work together.

Zigbee

A low-power wireless mesh standard, used in some commercial lighting systems.

Casambi

A widely used commercial wireless lighting platform, based on Bluetooth Low Energy.

KNX

An open building-automation standard covering lighting, blinds, heating and more.

LoRaWAN / NB-IoT

Long-range wireless networks used for outdoor, estate and street lighting.

Occupancy sensor

A sensor that detects people and switches or dims the lights.

Daylight harvesting

Dimming lights automatically when enough daylight enters the space.

Networked lighting control (NLC)

A system where fittings, sensors and controllers are connected and managed as one.

Luminaire-level lighting control (LLLC)

Every fitting has its own sensor and controller, while still being networked.

Building Energy Code (BEC)

EMSD's code for minimum energy efficiency of building services in Hong Kong. The current edition is BEC 2024.

Sources

The figures above come from published sources. The savings studies are from the United States. Links were checked in November 2026.

Talk to us

Matsushima Lighting has lit Hong Kong commercial, industrial and outdoor projects since 2006. If you are planning a new project, a fit-out or a retrofit and want to talk through lighting options, including controls, we are happy to help.

Call us on +852 2951 0038, WhatsApp +852 9635 1145, email enquiry@matsushima.hk, or use our contact form. Our office is open Monday to Friday, 9:00 to 18:00, at Rm 1805-06, 18/F, Hollywood Plaza, 610 Nathan Road, Mong Kok.

 
 
 

留言


這篇文章不開放留言。請連絡網站負責人了解更多。